The Atlas Copco QAS 200 JD T4F generators are prime power, multi-voltage, sound attenuated, mobile generators. They are powered by a John Deere T4 Final liquid-cooled, six-cylinder diesel engine.
The units consist of an alternator, diesel engine, cooling system, electrical distribution and control systems - all enclosed within a sound attenuated enclosure fabricated from powder coated steel with zinc rich primer. 6000 hour salt spray tested. A broad range of undercarriage formats and options are available. Special attention has been given to the overall product quality, user friendliness, ease of serviceability, and economical operation to ensure best in class total cost of ownership.
All QAS generators include the latest Tier 4 Final engine and have a footprint that is up to 20 percent smaller than the previous generation. The starting mechanism ensures that stable power is achieved in less than six seconds.
Generator | Units | QAS 200 JD | |
Frequency | Hz | 50 | 60 |
Rated Prime Power 3Ø (600,480,240V @ 60Hz, 400V @ 50Hz) | kW/ kVA | 134/168 | 160/200 |
Rated Standby Power 3Ø (600,480,240V @ 60Hz, 400V @ 50Hz) | kW/ kVA | 147/185 | 176/220 |
3Ø Power Factor | 0.8 | 0.8 | |
3Ø Voltage @ 600V (Series Star w/Neutral) | V | - | 600Y/346 |
Amp Capacity @ 600V/60Hz | A | - | 192 |
3Ø Voltage @ 480V (Series Star w/Neutral) | V | - | 480Y/277 |
Amp Capacity @ 480V/60Hz | A | - | 241 |
3Ø Voltage @ 240-208V (Parallel Star w/ Neutral) | V | - | 240Y/139 - 208Y/120 |
Amp Capacity @ 240V/Hz | A | - | 481 |
Amp Capacity @ 208V/Hz | A | - | 500 |
Rated Prime Power 1Ø | kW/ kVA | - | 102/102 |
1Ø Power Factor | - | 1.0 | |
1Ø Voltage @ 120-240V (Zig-Zag) | V | - | 240/120 |
Amp Capacity @ 240V | A | - | 425 |
Amp Capacity @ 120V | A | - | 2 x 425 |
3Ø Voltage @ 400V (Series Star w/Neutral) | V | 400Y/231 | - |
Amp Capacity @ 400V/50Hz | A | 243 | - |
Performance Class (acc. ISO 8528-5:1993) | G2 | G2 | |
Single Step Load Acceptance (0-PRP) @60Hz | kW(%) | 89.8 (67%) | 113(70.6%) |
Sound Pressure Level @ 23’(7 m) @ 75% Load2 | dB(A) | 69 | 71 |
Alternator (4 Pole, 12 Wire) | Leroy Somer | LSA 44.3 VL 13 | |
Excitation | AREP (auxiliary winding) | ||
Automatic Voltage Regulator (+/- 0.5%) | Leroy Somer | D350 | |
Insulation | Class H | ||
Main Breaker - Shunt Trip | A | 500 | |
Power Distribution – Terminal Board | 5 Wire (L1, L2, L3, N, Ground) | ||
Terminal Board Connections | Bare Wire Terminals | ||
Maximum Terminal Cable Size | 350MCM | ||
Convenience Receptacles | (2) NEMA 5-20R & (3) 125/250V 50A CS6364 |
||
Engine | Units | QAS 200 JD |
Model | John Deere | 6068HFG05 |
US EPA Tier | Tier 4 Final | |
Displacement | L | 6.8 |
Cylinders | # | 6 |
Continuous Engine Power Output | HP (kW) | 235 (175) |
Gross Engine Power Output | HP (kW) | 257 (192) |
Rated Speed | RPM | 1800 |
Engine Control | ECU | |
Aspiration | Turbocharged w/ Intercooler | |
Engine oil capacity4 | US Gal (L) | 8.6 (32.5) |
Engine coolant capacity | US Gal (L) | 10.5 (39.7) |
Maximum Ambient Temperature (@ Sea Level)5 | °F (°C) | 122 (50) |
Min. Starting Temp (w/o heater) | °F (°C) | 14 (-10) |
Minimum Starting Temperature (with heater)6 | °F (°C) | -13 (-25) |
Electrical System (Negative Ground) | V | 24 |
Engine Alternator Output | A | 60 |
Battery Capacity (Cold Cranking Amps) | A | (2) 685 |
Fuel System | Units | QAS 200 JD | |
Fuel Consumption @ 25% load 50Hz / 60Hz | US Gal/hr (L/hr) | 3.2 (12.0) | 4.1 (15.4) |
Fuel Consumption @ 50% load 50Hz / 60Hz | US Gal/hr (L/hr) | 5.2 (19.7) | 6.4 (24.2) |
Fuel Consumption @ 75% load 50Hz / 60Hz | US Gal/hr (L/hr) | 7.0 (26.5) | 8.2 (31.0) |
Fuel Consumption @ 100% load 50Hz / 60Hz | US Gal/hr (L/hr) | 8.8 (33.3) | 10.8 (41.0) |
Fuel Type | Ultra-Low Sulfur Diesel ONLY | ||
Fuel Tank Capacity | US Gal (L) | 290 (1068) | |
Fuel Autonomy @ 75% load and 90% of tank capacity | Hr | 37.3 | 31.7 |
DEF Tank Capacity | US Gal (L) | 25 (94.6) | |
DEF Autonomy @ 75% load and 95% of DEF capacity |
Hr | 90.0 |
Generators can supply power to temporary structures and construction equipment that require electricity to operate. The QAS 200 Portable Generator is suitable for less complex projects such as small road construction, single family houses, and low-rise apartments.
Outdoor events such as festivals, sporting events, and the like depend on high-performing generators to keep the function running smoothly. Easy-to-use interface and water-resistant design ensure inclement weather or poor handling will not impede the event.
Natural disasters and inclement weather are the main causes of power outages. Protect yourself against an outage with our QAS 200 Generator. With an intuitive system controller, you have advanced warning and alert parameters for added safety.